Skip to content

We're upgrading our operations to serve you better. Orders ship as usual from Laval, QC. Questions? Contact us

Bitcoin accepted at checkout  |  Ships from Laval, QC, Canada  |  Expert support since 2016

PSU_ERR Critical

ASIC Miner – Circuit Breaker Tripping

ASIC miner tripping a circuit breaker — a mains-side failure, not a miner failure. Root causes cluster in six buckets: continuous-load rule violation (80% / NEC 210.19 / CEC 8-104), shared-circuit aggregation, voltage sag forcing current up, PSU inrush on power-on, aged or marginal breaker, or AFCI/GFCI false-trip on switching-supply EMI. Fixing it requires diagnosing the panel, not the miner.

Critical — Immediate action required

Affected Models: All ASIC miners on residential or light-commercial power: Antminer S9 / L3+ / S17 / S19 / S19j Pro / S19 XP / S19k Pro / S21 / S21 Pro / L7 / T21, Whatsminer M30S / M50S / M60S, Avalon 1166 / 1246, Bitaxe farms, Bitcoin space-heater builds

Symptoms

  • Breaker trips within seconds of powering on the miner (inrush-current trip signature)
  • Breaker trips 10-90 minutes after power-on, once the miner is at full hashrate (thermal / steady-state trip)
  • Trip correlates with another appliance kicking on — A/C compressor, dryer, EV charger, well pump, electric oven
  • Multiple miners on the same branch: breaker holds for one, trips on two
  • `kern.log` / cgminer / `bmminer` logs `ERROR_POWER_LOST` with timestamps matching the moment the breaker popped
  • Breaker feels warm or hot to touch after a trip (hot breaker = marginal breaker or loose bus-stab; this is the dangerous one)
  • Faint ozone / hot-plastic smell near the panel on repeated trips (stop immediately, de-energize, Tier 4)
  • Breaker trips immediately every plug-in with no load — short on the miner / PSU / cable side, not overload
  • AFCI or GFCI breaker trips when the miner hashes but holds for a vacuum or space heater at similar wattage (EMI false-trip)
  • Wire insulation, outlet faceplate, or plug body shows discoloration / scorch / melting
  • Multiple breakers trip together on a tandem / split-bus panel — neutral or ground path issue, not a miner issue
  • In cold weather the trip vanishes; in warm weather it returns (panel ambient derating)
  • Evening-only trips (4-9 PM) correlating with neighbourhood peak load — voltage sag pulling current up

Step-by-Step Fix

1

Do the load math before you do anything else. Read the miner's nameplate wattage and divide by the circuit voltage (120 or 240) to get steady-state amps. Multiply by 1.25 per NEC 210.19(A)(1) / CEC 8-104(5) continuous-load rule. If that number exceeds the breaker rating, the circuit is too small — the breaker is doing its job correctly and you need a bigger circuit, not a bigger breaker. This step alone resolves 40% of tickets before a multimeter is even unboxed.

2

Stagger power-on. If multiple miners are on the same circuit (they shouldn't be, but we see it), unplug all but one. Power the first on, wait 30 seconds, plug the next in, power it on, wait another 30 seconds. Eliminates stacked inrush current. If the breaker holds when staggered but trips on simultaneous cold-start, you have an inrush problem that a sequenced PDU fixes without touching the panel.

3

Audit everything else on that breaker. Turn the miner off, flip the suspect breaker off, walk the building. Every dead outlet, light, and hardwired load is on that breaker — map it on paper. You will almost always find something you forgot: garage freezer, furnace blower transformer, PoE switch, security system. For any miner above 2000W you need a truly dedicated circuit; shared is the #1 root cause in D-Central's ticket queue.

4

Check cable and outlet condition. Unplug, inspect. Discoloration on the plug blades, browning on the outlet face, warm-to-touch faceplate, or a scorch smell near the receptacle all indicate a cable or outlet-level failure compounding the breaker issue. Replace the outlet with a hospital-grade 5-20R (NEMA 6-20 for 240V) for $15-25 CAD; replace the cable if blades are discolored. Do this before any panel-level work — it's often the actual problem.

5

Move to a known-good circuit to confirm. If you have a dedicated 240V dryer outlet, EV charger outlet, or range outlet, repurpose it with an appropriate adapter for diagnostic purposes only (do not leave it this way) and run the miner from there. If the trip vanishes, the original circuit is the problem. If it persists, the miner or PSU is the problem, not the circuit. This cleanly splits the diagnostic tree.

6

Clamp-meter the running load. True-RMS clamp on the single hot conductor, miner at full hashrate, record amps over at least 5 minutes of steady-state operation. Compare to (breaker rating) × 0.80. Over budget means the circuit is undersized — go fix the circuit, not the miner. Under budget means you have a secondary issue (sag, inrush, aged breaker, AFCI false-trip) — continue to step 7.

7

Log voltage for 24 hours with a Kill-A-Watt P4400 or data-logging voltmeter. Record min/max. Expect 235-245V on 240V split-phase, 115-120V on 120V residential, 202-212V on 208V commercial. Min below 230V on 240V or below 112V on 120V under load means service-side voltage sag is forcing higher current through your PSU — that is the breaker's point of view even if your nameplate math said you had margin.

8

Peak-hold inrush measurement. Clamp meter in peak-hold mode, power-cycle the miner three times with 30 seconds between cycles, record peaks. Typical Antminer / Whatsminer / Avalon sees 45-80A peak for 10-30 ms. Peaks above 60A on a 15A breaker or above 90A on a 20A breaker will trip weak or aged breakers even though steady-state is fine. If this is your signature, a sequenced PDU ($250-500 CAD) is the fix.

9

Test AFCI / GFCI breakers via their push-to-test button. If push-to-test does not trip the breaker, the electronics are dead and the breaker must be replaced. If push-to-test works but the miner still nuisance-trips at hash-time (and a space-heater or kettle at similar wattage holds), the AFCI is responding to switching-supply EMI. Move the miner to a non-AFCI-protected circuit if code permits, or install a Schaffner FN 2090 line-level EMI filter.

10

Torque-audit the outlet. Kill power at the breaker. Pull the outlet out of the box. Verify the hot and neutral conductors are torqued to manufacturer spec on the outlet screws — typically 10-14 in-lb for residential-grade. Loose connections add resistance, resistance adds heat under continuous miner load, heat further loosens the connection. A single 1/4-turn retighten on an aging outlet has saved more miners from breaker-trip cycles than any firmware update.

11

Pull a dedicated 240V / 20A circuit to the miner location. Run 12 AWG copper minimum; check local code for voltage drop over distance (long runs need 10 AWG). Terminate on a new breaker on the opposite leg from any nearby heavy load. CEC 8-104(5) 80% continuous-load rule applies. For multi-miner setups pull 240V / 30A with 10 AWG and budget two miners per circuit, not three. This is the real fix for roughly 70% of tripping-breaker tickets D-Central sees. Licensed-electrician work.

12

Replace the suspect breaker with a same-brand, same-type, same-rating unit. Siemens / Square D / Eaton / Schneider / Federal Pioneer (on old Canadian panels) — do not mix brands; each manufacturer's bus-stab geometry differs, and mixing is a code violation in most jurisdictions. Torque the breaker-to-bus connection and the conductor-to-breaker screw to manufacturer spec. Parts cost $15-40 CAD; full electrician visit $150-400.

13

Install a sequenced / inrush-limited PDU for multi-miner rigs. A PDU with per-outlet relay sequencing (APC AP7911B class or equivalent) staggers each outlet's energize by 250-1000 ms. Eliminates stacked inrush, smooths the aggregate draw curve, and provides per-outlet amp telemetry on network-capable units. Overkill for a single miner; essential for any 4-to-10 rig basement operation. Runs $250-500 CAD once and removes the inrush variable permanently.

14

For AFCI-false-trip circuits, add a line-level EMI filter. Schaffner FN 2090-16-06 or equivalent, mounted between the breaker output and the outlet inside a NEMA 1 enclosure. Attenuates the 1-30 MHz switching-supply harmonics that trip AFCI electronics. This is advanced work and misses the cleaner fix (move the miner to a non-AFCI circuit), so deploy only where code forces AFCI on the only location you can reach.

15

For chronic voltage-sag situations, install a buck-boost autotransformer that compensates +/- 10% line variation. $250-600 CAD depending on kVA. Protects the PSU from sag-driven overcurrent at the cost of a single additional point of failure. Niche tool — most situations are better solved at the panel by moving the miner closer to the service entrance or upgrading the feeder. Consider only after step 7 (voltage logging) confirms chronic sag beyond utility tolerance.

16

Stop DIY. Panel is Federal Pacific / Federal Pioneer Stab-Lok / Zinsco / Pushmatic / unknown no-brand; repeated trips have left the breaker discolored or cracked; the panel cover is warm to touch even with the miner off; or you smell hot plastic / ozone at the panel. Any of these means de-energize the main and call a licensed electrician today. This is not a D-Central repair job — it's a trade-ticketed electrical-safety job that we do not do remotely.

17

When the miner is the cause. If Tier 1-3 isolates the problem to the miner or PSU side (short on hashboard power input, PSU inrush outside normal bounds, internal PSU fault), book a D-Central ASIC Repair slot. On the bench we test-fixture the PSU, audit bulk caps for ESR drift, check for pre-fail shorts on the hashboard power input plane, and return a unit that draws clean steady-state and clean inrush.

18

Ship safely. Send the PSU only (not the full miner) in a double-box with at least 5 cm foam on every side, anti-static bag inside. Include a note with: breaker type / brand / rating, observed trip pattern (instant-on vs delayed vs intermittent), measured peak inrush if you have it, measured rail voltage at idle and under load, and the make/model of any PDU in the chain. Pre-flight info saves bench diagnostic time and that saves you repair cost.

When to Seek Professional Repair

If the steps above do not resolve the issue, or if you are not comfortable performing these repairs yourself, professional service is recommended. Attempting advanced repairs without proper equipment can cause further damage.

Related Error Codes

Still Having Issues?

Our team of Bitcoin Mining Hackers has been repairing ASIC miners since 2016. We have seen it all and fixed it all. Get a professional diagnosis.