Bitmain Antminer S23 Hyd 580T official reference
Exact S23 Hyd model 580T-10 reference: 580 TH/s, 5,510 W, 9.5 J/TH and exact 12 A three-phase/OD10 liquid-loop boundaries.
Quick answer
The Bitmain Antminer S23 Hyd 580T official reference is a Bitcoin miner rated about 580 TH/s at roughly 5,510 W (about 9.5 J/TH).
Latest Generation Hardware
This is a newer generation of mining hardware using recent ASIC chip technology. Compare efficiency, hashrate, and power draw against older generations before choosing a deployment plan.
Lower J/TH means lower electricity cost per unit of hashrate. Compare efficiency alongside purchase cost, noise, voltage, firmware support, and current network difficulty.
Full Specifications
| Model | Bitmain Antminer S23 Hyd 580T official reference |
|---|---|
| Model Number | Antminer S23 Hyd model 580T-10 |
| Manufacturer | Bitmain |
| Algorithm | SHA-256 |
| Hashrate | 580 TH/s |
| Power Consumption | 5,510 W |
| Calculated nominal efficiency | 9.5 J/TH |
| Cooling | Hydro |
| Voltage Range | 3-phase 380-415 V AC; 50-60 Hz; 12 A |
| Dimensions | 410 x 170 x 209 mm |
| Weight | 13.5 kg net |
| Interface | RJ45 Ethernet 10/100M |
| Status | Exact OEM manual reference |
Exact S23 Hyd. reference: model S23 Hyd., version 580T-10, SHA256 for the BTC/BCH/BSV source lane.
| Typical hashrate | Wall power at 35°C coolant inlet | Wall efficiency |
|---|---|---|
| 580 TH/s | 5,510 W | 9.5 J/TH |
Actual hashrate fluctuates ±3%; actual wall power and efficiency fluctuate ±5%.
Exact facility and liquid-loop boundary
| Electrical | 3-phase, 380–415 V AC, 50–60 Hz, 12 A |
|---|---|
| Coolant inlet | 20–50°C; 8.0–10.0 L/min; pressure no more than 3.5 bar |
| Coolant / pH | Antifreeze 7.0–9.0; pure water 6.5–7.5; deionized water 8.5–9.5 |
| Pipe connector | OD10 |
| Network | RJ45 Ethernet 10/100M |
| Dimensions / packed | 410 × 170 × 209 mm / 570 × 316 × 430 mm |
| Net / gross | 13.5 / 14.8 kg |
| Storage / humidity | -20–70°C / 10–90% RH non-condensing |
A qualified facility designer must verify the exact 580T-10 label, three-phase supply, protection, grounding, disconnect, connector, coolant chemistry, pH, temperature, flow, pressure, pipe, filtration, maintenance, and heat rejection. U3S23H values do not apply.
Firmware and service
- Exact S23 Hyd. manual v1.0.6.
- Exact-model firmware selector.
- Fault finder; repair triage; S23 evidence hub.
No compatibility, tuning, economics, residential, heat-use, or other-model claim is asserted.