Wire-Sizing & DC Voltage-Drop Reference (ASIC Miners & Solar)
Wire sizing for a mining circuit comes down to two questions that have to be answered together: can the conductor safely carry the current without overheating (ampacity), and will it deliver usable voltage at the far end of the run (voltage drop)? This reference pairs the published ampacity figures from NEC 2023 Table 310.16 with the DC resistance values from Chapter 9, Table 8, so you can check both at once for copper and aluminum from 14 AWG up to 4/0. The numbers are the code values, not estimates — but they are a starting point for planning, not a substitute for a licensed electrician signing off on your install.
How to read the ampacity columns
Every conductor in the table shows three ampacities — the 60 °C, 75 °C, and 90 °C insulation columns. The temperature does not describe how hot your room is; it describes the insulation rating of the wire and, more importantly, the rating of the terminals it lands on. You must size to the lowest temperature rating in the path. Most breakers, lugs, and equipment terminals are rated 75 °C, so the 75 °C column is the realistic limit for the majority of installs even when the wire itself is rated 90 °C THHN.
Two further rules trim the headline numbers down. For small conductors, NEC 240.4(D) caps the overcurrent device regardless of the ampacity column: 14 AWG copper is limited to 15 A, 12 AWG copper to 20 A, and 10 AWG copper to 30 A. And before you commit to a size, the ampacity must still be derated for ambient heat and for bundling several current-carrying conductors together, per NEC 310.15. A run inside a hot, crowded conduit behind a row of machines carries less than the table suggests.
Working the DC voltage-drop math
The resistance column is the second half of the calculation. For a DC run, voltage drop across the pair of conductors is Vdrop = 2 × L × I × R / 1000, where L is the one-way length of the run in feet, I is the current in amps, and R is the DC resistance in ohms per 1000 feet from the table. The factor of two accounts for current travelling out on one conductor and back on the other.
A common planning target is to keep any single branch circuit at or below a 3% drop and the whole path — feeder plus branch — at or below 5%. On a long DC home-run to a low-voltage device, voltage drop, not ampacity, is usually what forces you up to a heavier conductor. If your calculated drop creeps past target, step up one wire size and recompute rather than accepting marginal voltage at the load. The resistance figures shown are taken at 75 °C; a warmer conductor has slightly higher resistance and a touch more drop, which is a sensible direction to err.
Copper, aluminum, and the Canadian context
Aluminum carries roughly the same job at a lighter weight and lower cost, but at any given size it has lower ampacity and higher resistance than copper — so an aluminum run typically lands one or two sizes larger than the copper equivalent for the same load and length. Aluminum also demands proper terminations: listed connectors, an anti-oxidant where specified, and torque to the marked value. Note that NEC Table 310.16 does not list aluminum smaller than 12 AWG, so for the smallest circuits copper is the practical choice.
If you are wiring in Canada, the Canadian Electrical Code governs: Table 2 for copper and Table 4 for aluminum. The CEC ampacities are comparable to the NEC figures with minor differences, but the CEC and your local authority having jurisdiction always take precedence over any table reproduced here. Treat this page as a way to plan and sanity-check a run, then have a licensed electrician verify the final conductor size, overcurrent protection, derating, and terminations for your specific installation.
Quick answer
This reference gives the NEC/CEC ampacity (at 60, 75 and 90 C terminal ratings) and DC resistance for copper and aluminum conductors from 14 AWG to 4/0, so you can size the wiring for a Bitcoin miner's circuit or an off-grid solar DC run. Read the ampacity at your terminal's temperature rating, respect the NEC 240.4(D) small-conductor overcurrent caps, and use the voltage-drop formula below to keep a DC run within the common 3% branch / 5% total targets.
Reference only, not a stamped design. Have a licensed electrician verify all conductor sizing, overcurrent protection, derating and terminations, and follow your local code — the Canadian Electrical Code (CEC) in Canada and the authority having jurisdiction (AHJ) everywhere.
Heads-up: ampacities are at a 30 C ambient with no more than three current-carrying conductors; apply NEC 310.15 / CEC Table 5A–5C derating for higher ambients or bundling before final selection. Size to your equipment's terminal-temperature column (often 75 C).
Download CSV Download JSON REST API →
| AWG | Material | 60°C | 75°C | 90°C | DC Ω/1000ft | Notes |
|---|---|---|---|---|---|---|
| 14 | Copper | 15 A | 20 A | 25 A | 3.07 | NEC 240.4(D) limits 14 AWG Cu overcurrent protection to 15 A regardless of the 75/90 C ampacity. Resistance is uncoated solid Cu at 75 C (Ch. 9 Table 8); 7-strand reads ~3.14. |
| 12 | Copper | 20 A | 25 A | 30 A | 1.93 | NEC 240.4(D) limits 12 AWG Cu overcurrent protection to 20 A. Resistance is uncoated solid Cu at 75 C; 7-strand reads ~1.98. |
| 10 | Copper | 30 A | 35 A | 40 A | 1.21 | NEC 240.4(D) limits 10 AWG Cu overcurrent protection to 30 A. Resistance is uncoated solid Cu at 75 C; 7-strand reads ~1.24. |
| 8 | Copper | 40 A | 50 A | 55 A | 0.764 | Resistance is uncoated solid Cu at 75 C; stranded 8 AWG reads ~0.778. CEC Table 2 gives comparable values. |
| 6 | Copper | 55 A | 65 A | 75 A | 0.491 | Resistance is uncoated stranded Cu at 75 C (Ch. 9 Table 8). |
| 4 | Copper | 70 A | 85 A | 95 A | 0.308 | Resistance is uncoated stranded Cu at 75 C. |
| 3 | Copper | 85 A | 100 A | 110 A | 0.245 | Resistance is uncoated stranded Cu at 75 C. |
| 2 | Copper | 95 A | 115 A | 130 A | 0.194 | Resistance is uncoated stranded Cu at 75 C. |
| 1 | Copper | 110 A | 130 A | 145 A | 0.154 | Resistance is uncoated stranded Cu at 75 C (19-strand). |
| 1/0 | Copper | 125 A | 150 A | 170 A | 0.122 | Resistance is uncoated stranded Cu at 75 C (19-strand). |
| 2/0 | Copper | 145 A | 175 A | 195 A | 0.0967 | Resistance is uncoated stranded Cu at 75 C (19-strand). |
| 3/0 | Copper | 165 A | 200 A | 225 A | 0.0766 | Resistance is uncoated stranded Cu at 75 C (19-strand). |
| 4/0 | Copper | 195 A | 230 A | 260 A | 0.0608 | Resistance is uncoated stranded Cu at 75 C (19-strand). |
| 14 | Aluminum | — | — | — | — | NEC Table 310.16 does not list aluminum smaller than 12 AWG; 14 AWG aluminum building wire is not a standard listed size. Use copper at this size. |
| 12 | Aluminum | 15 A | 20 A | 25 A | 3.18 | NEC 240.4(D) limits 12 AWG Al overcurrent protection to 15 A. Resistance is Al at 75 C (Ch. 9 Table 8). CEC Table 4 gives comparable values. |
| 10 | Aluminum | 25 A | 30 A | 35 A | 2 | NEC 240.4(D) limits 10 AWG Al overcurrent protection to 25 A. Resistance is Al at 75 C. |
| 8 | Aluminum | 35 A | 40 A | 45 A | 1.26 | Resistance is Al at 75 C (Ch. 9 Table 8). |
| 6 | Aluminum | 40 A | 50 A | 55 A | 0.808 | Resistance is Al at 75 C. |
| 4 | Aluminum | 55 A | 65 A | 75 A | 0.508 | Resistance is Al at 75 C. |
| 3 | Aluminum | 65 A | 75 A | 85 A | 0.403 | Resistance is Al at 75 C. |
| 2 | Aluminum | 75 A | 90 A | 100 A | 0.319 | Resistance is Al at 75 C. |
| 1 | Aluminum | 85 A | 100 A | 115 A | 0.253 | Resistance is Al at 75 C. |
| 1/0 | Aluminum | 100 A | 120 A | 135 A | 0.201 | Resistance is Al at 75 C. |
| 2/0 | Aluminum | 115 A | 135 A | 150 A | 0.159 | Resistance is Al at 75 C. |
| 3/0 | Aluminum | 130 A | 155 A | 175 A | 0.126 | Resistance is Al at 75 C. |
| 4/0 | Aluminum | 150 A | 180 A | 205 A | 0.1 | Resistance is Al at 75 C. |
DC voltage-drop math
For a DC run with one-way length L (feet), current I (amps) and conductor DC resistance R (Ω per 1000 ft):
Vdrop = 2 × L × I × R ÷ 1000
The factor of 2 accounts for the supply and return legs. Percentage drop = Vdrop ÷ Vsource × 100. Keep any single branch at or below 3% drop and the combined feeder-plus-branch path at or below 5% total. A long low-voltage run (for example a 12 V solar circuit) is almost always voltage-drop-limited, not ampacity-limited — step up a size or two.
Sources: NEC 2023 (NFPA 70) Table 310.16, Chapter 9 Table 8, and 240.4(D); cross-referenced with the Canadian Electrical Code (CEC) Tables 2 and 4. Planning the circuit itself? See our Canadian landed-cost calculator and the open data hub. This is general information, not a stamped electrical design.
Related products, repair, and setup paths
- how D-Central diagnoses ASIC repairs
- ASIC troubleshooting library
- ASIC manuals and repair guides
- replacement hashboards
- ASIC control boards
- ASIC power supplies
- S19 family replacement hashboard
- C52 replacement control board
- APW12 S19 power supply
- immersion cooling hub
- home immersion cooling guide
- ASIC miners for immersion planning
- ASIC cooling parts
- airflow shroud before immersion
- compare miner specs in the database
- ASIC repair support
Last reviewed June 28, 2026.
